Product Manual V1.2
© Copyright Brainboxes Ltd
Page 63 of 100
$aa0Ci
Applies to: ED-549
Description:
Command to perform a zero calibration on a specified channel.
Command Syntax:
$aa0Ci[CS](CR)
$
Delimiter character
aa
Address of the device to be calibrated, in hexadecimal format (00 to FF)
0C
Command to perform the zero calibration
i
Channel on which to perform the zero calibration
[CS]
Checksum
(CR)
Carriage Return
Response:
Valid Command: !aa[CS](CR)
Invalid Command: ?aa[CS](CR)
!
Delimiter for a valid command
?
Delimiter for an invalid command
aa
Address of the device which responded
[CS]
Checksum
(CR)
Carriage Return
Examples:
Send the command to set the zero calibration of channel 0 to the voltage being applied to the line.
Command: $010C0(CR)
Response: !01(CR)
Note: Calibration must be enabled using ~aaEV before using this command.