37
Fluid installation
7.3.3 Finalise the installation of the 8035 Batch
→ Wire the device and switch it on (see chap. 8).
→ Set the K-factor or determine it with Teach-In (see chap. 10.7.3 or 10.7.4).
7.4 Installation of the dosing controller SE35 Batch on
the sensor-fitting S070 or S077
The dosing controller SE35 Batch is installed on the pipes using the sensor-fitting S070 or S077. The dosing
controller SE35 Batch is assembled on the sensor-fitting S070 or S077 by a quarter-turn system:
1. Install the sensor-fitting S070 or S077 on the pipes,
2. Install the dosing controller SE35 Batch on the sensor-fitting S070 or S077,
3. Finalise the installation.
7.4.1 Install the sensor-fitting S070 or S077 on the pipes
→ Select a sensor-fitting S070 or S077 suitable for the viscosity of the fluid.
To select a sensor-fitting, refer to the technical data sheet for the relevant sensor-fitting.
attention
Risk of damage when installing the sensor-fitting.
▶ Follow the installation instructions given in the Operating Instructions for the sensor-fitting.
→ Install the sensor-fitting S070 or S077 on the pipes in such a way that:
- the axles of the oval gears are set horizontally, as shown in Fig. 14,
- the installation instructions given in the Operating Instructions for the relevant sensor-fitting are respected.
Correct Incorrect
Fig. 14 : The axle of the oval gears must be horizontal
English
Type 8025 - 8035 - SE35 BATCH