45
Electrical installation and Wiring
8.4 Default position of the selectors
Only move the selectors when the power supply is off.
Tab. 1 : Default positions of selectors "SENSOR SUPPLY", "LOAD" and "SENSOR TYPE"
Selector Default position
SENSOR SUPPLY
A
L+
LOAD
B
2.2KOhms
SENSOR TYPE
C
NPN/PNP
8.5 Terminal assignment and use of the selectors
2
A
1
5
B
C
6
CURRENT
SOURCESINK
BINARY
PE PEPE
PE
DI1
DI2
DI3
DI4
DO4
ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
Iout
PULSE
DO1
Supply
12..36Vdc
Univ
Batch
(AO1)
SUPPLY
NC
COIL
PULSE
INPUT
NPN/PNP
213PE
+-
SENSOR
SUPPLY
LOAD
+5V
L+
(L+)-12V
COIL/PNP
39K
470
2.2K
SENSOR TYPE
COIL NPN/PNP
DO2
DO3
OFFON
3
4
Terminal block 1
NC: not connected
L+: V+ (positive voltage)
L-: 0V (power supply ground)
PE: protective earth, factory wired
P-: negative transistor output (DO1)
P+: positive transistor output (DO1)
Terminal block 2
PE: shieldings of the power supply cable and the
input / output cables
Terminal block 3: wiring the DO2 relay output.
Terminal block 4: wiring the DO3 relay output.
Connector 5: connection of the flow sensor
Terminal block 6 "BINARY"
DI1 to DI4: 4 digital inputs
DO4: transistor output
ISOG: ISOGND, ground common to the 4
digital inputs and the transistor output DO4.
PE: cable shielding
Selector
A
: see chap. 8.6.
Selector
B
: see chap. 8.6.
Selector
C
: see chap. 8.6.
Fig. 22 : Terminal assignment of a 12...36 V DC fed version for the 8025 Batch in compact version, for the 8035 Batch and
for the SE35 Batch
English
Type 8025 - 8035 - SE35 BATCH