72
Operating and functions
• If the generation of alarms (alarm "DURING") for problems occurring during a dosing has been activated
(see chap. 10.7.16), an alarm is generated if there is no flow rate measured in the pipe whereas the
valves are open. See chap. 11.3.4 to solve the problem.
• If the generation of alarms (alarm "AFTER") for problems occurring at the end of the dosing has been
activated (see chap. 10.7.17), an alarm is generated if there is still flow in the pipe whereas the valves
are closed. See chap. 11.3.4 to solve the problem.
Process level
BAtCH A
OK Y/N
89.2 L
→ Choose the dosing quantity.
→ Confirm.
→ Choose "OK Y" to start the dosing.
→ Confirm.
The dosing quantity is counted down (the dosing units
blink).
→ To read the flow rate measured in the pipe, press
or
0......9
.
→ To read the total dosing quantity, press
or
0......9
once.
→ To interrupt the dosing, see Fig. 43.
V1
V7
REtURN
0......9
→ Confirm.
When the dosing is finished:
• the dosing units do not blink any more,
• and the valves are closed.
→ To go back to the Process level in order to start a
new dosing, press
ENTER
.
0.1 L
Fig. 42 : Doing a dosing in dosing modes "LOC. MEM." or "MEM.+MANU."
English
Type 8025 - 8035 - SE35 BATCH