49
Start-up
Sub-
index
Name Description
Access type
Data type
Data memory
Factory
reset
0x9 Reset command
Reset counters:
The resettable counters can be reset as
follows:
Bit0 = 1: Reset switching cycles
Bit1 = 1: Reset travel accumulator
Bit2 = 1: Reset operating time counters
Bit3 = 1: Reset number of
opening time timeouts
Bit4 = 1: Reset number of
closing time timeouts
Bit5 = 1: Import measured switching
times (0xA and 0xB).
Source dependent on
setting in 0x15
Bit6 = 1: Reset number of
switching time timeouts
RW UINT8
0xA Opening time limit
Maximum opening time [ms]:
Congurableopeningtimefromwhich
a warning (active) should be generated
to indicate potential faults in the system
(e.g. pilot pressure too low, excessive
friction in actuator, etc.).
RW UINT16 x x
0xB Closing time limit
Maximum closing time [ms]:
Congurableclosingtimefromwhicha
warning (active) should be generated to
indicate potential faults in the system
(e.g. pilot pressure too low, excessive
friction in actuator, etc.).
RW UINT16 x x
0xC Time tolerance
Toleranceforcongurableswitching
times [%]:
Speciesthetolerancefortheparam-
eters “opening time limit” and “closing
time limit”, from which point an active
warning is generated.
RW UINT8 x x
0xD Opening time error
counter
Number of times opening time threshold
exceeded (resettable):
Valueconguredin“openingtimelimit”+
“time tolerance” has been exceeded
RO UINT32
0xE Closing time error
counter
Number of times closing time threshold
exceeded (resettable):
Valueconguredin“closingtimelimit”+
“time tolerance” has been exceeded
RO UINT32
0xF Teach function counter
Number of teach functions performed
RO UINT32