3–27 62-11640
MAX OFF TIME: OFF
10MINS
TO
255MINS (in 1 minute in-
crements)
OFF - There is no maximum off time.
When a minute value is selected, this is the longest amount of
time the unit will remain off during a (Perishable or Frozen or
both) Auto Start/ Stop Off Cycle. When this time expires, the
unit will restart and run for the Minimum Run Time, regardless
of any temperature change inside the compartment.
SWITCH TO DIESEL: YES
NO
This will override the No A/C Power Configuration parameter
when this functional parameter indicates No so that the system
will shutdown.
FROZEN SHUT-
DOWN OFFSET:
0°F to 1.1°F
(0°C to 0.6°C) (in 0.1°F or
C increments)
This only applies to Frozen Setpoints in Start-Stop operation.
This offset is the number of degrees below setpoint that the
unit will run before cycling off. This will allow for a lower aver-
age compartment temperature when considering temperature
rises during off cycles.
SLEEP MODE For complete instructions on entering and setting parameters for Sleep Mode refer to Sec-
tion 3.18.
WAKE UP TIME OFF
ON
Set a time when Sleep Mode will wake up, ranging from 1 hour
to 8 days from current time.
OVERRIDES
OVERRIDE DOOR
SWITCH SHUTDOWN
(DS)
OVERRIDE REMOTE
SWITCH 1 SHUT-
DOWN (REMS1)
OVERRIDE REMOTE
SWITCH 2 SHUT-
DOWN (REMS2)
NO
YES
If the switches are all configured “Switch Not Installed”, this pa-
rameter will not display.
NO = the system will respond to the switch as configured.
YES = the configured action on activation of the switch will be
overridden and the action will be alarm only. The purpose of
this setting is to temporarily override the Configuration setting
in situations where shutdown or speed change is not desired.
NO S/B POWER SHUT DOWN UNIT
SWITCH TO DIESEL
Unit will switch to diesel when no voltage for 5 minutes if con-
figured to do so.
VIEWING PREFERENCES
DISPLAY TEMPERA-
TURE IN
°F
°C
Temperatures will display in either Fahrenheit (°F) or Celsius
(°C). (for North American Units, this function may be locked)
DISPLAY PRESSURE
IN
PSIG
BAR
Pressure will display in either psig or (bar). (for North American
Units, this function may be locked)
DATE FORMAT MM/DD/YYYY
DD/MM/YYYY
Date will display in either US (MM/DD/YYYY) or European
(DD/MM/ YYYY) format.
ALARM DESCRIP-
TIONS
YES
NO
YES = In the Driver Mode, the alarm code and alarm descrip-
tion will be displayed.
NO = In the Driver Mode, only the alarm code will be displayed.
CONTRAST 0 TO 63 (In single digit in-
crements)
35
Higher numbers increase the contrast of the display screen.
Table 3–2 Functional Parameters
FUNCTION PARAMETER
SELECTIONS
DESCRIPTION

Table of Contents

Other manuals for Carrier TRANSICOLD Vector 8500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier TRANSICOLD Vector 8500 and is the answer not in the manual?

Carrier TRANSICOLD Vector 8500 Specifications

General IconGeneral
BrandCarrier TRANSICOLD
ModelVector 8500
CategoryAutomobile Accessories
LanguageEnglish

Related product manuals