EasyManua.ls Logo

Carrier TRANSICOLD Vector 8500 - Figure 4.2 Range Lock Settings - Non Overlapping; Figure 4.3 Range Lock Settings - Overlapping

Carrier TRANSICOLD Vector 8500
326 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–11 62-11640
Figure 4.2 Range Lock Settings - Non Overlapping
The primary time that it is important to determine which
range is to be Range 1 and which is to be Range 2 is
when the ranges overlap each other.
In example 2 (see Section 4.3), the ranges have been
set to lock all setpoints into Start-Stop, except for a
small range between +32° and +42°F (0° and 5.6°C)
where the unit will always operate in Continuous.
Range 1 Minimum Temperature has been set for
+32°F (0°C), and Maximum Temperature of +42°F
(5.6°C). Range 2 has been set for a Minimum Tem-
perature of -22°F (-30°C) and a Maximum Temperature
of +89.6°F (32°C). The unit will switch to Continuous
when the setpoint is between +32° and +42°F (0° and
5.6°C) because, when the ranges overlap each other
the Range 1 settings will take priority.
Figure 4.3 Range Lock Settings - Overlapping
Range Lock 1 & 2
Range 2 is set for
0
to -22 F
(-17.8
to -30 C)
Range 1 is set for
28
to 55 F
(-2.2
to +12.8 C)
-30 -23.3 -17.8 -12.2 -6.7 4.4 10.0 15.6-1.1 21.1 26.7
C
-22 -10
0
10 20 40 50 60 0703
80
F
Range 2
Range 1
-30 -23.3 -17.8 -12.2 -6.7 4.4 10.0 15.6-1.1 21.1 26.7
C
-22 -10
0
10 20 40 50 60 0703
80
F
Range 1 always has priority
when Range 1 & 2 overlap
Range 1 is set for 32 to 42 F
(0
to 5.6 C)
Set for Continuous
Range 2 is set for -22 to
89.6
F (-30 to 32 C)
Set for Start-Stop
Range
1
Range 2

Table of Contents

Other manuals for Carrier TRANSICOLD Vector 8500

Related product manuals