62-11640 4–4
NOTE
The control system may be locked so that
the unit will always operate in Start-Stop
whenever the setpoint is within a specific
range. Refer to Range Lock (Section
4.10.2) for additional information.
4.5.1 Start-Stop Configuration
Start-Stop Operation is dependent on both Configura-
tion and Functional Parameter settings. The first set-
ting to be considered is the START-STOP
PARAMETERS Configuration. This setting determines
control actions when in the Perishable Range or Fro-
zen Range. The available settings are TOGETHER
and SEPARATE.
When SEPARATE is chosen the control action
will be different, depending on whether the set-
point is in the Perishable Range or in the Frozen
Range (refer to Section 4.7.1).
When TOGETHER is chosen, the same settings
apply to any setpoint.
If TOGETHER is selected, then the following Func-
tional Parameter values will be available for use:
MINIMUM RUN TIME
MINIMUM OFF TIME
RESTART TEMPERATURE
OVERRIDE TEMP
MAXIMUM OFF TIME
FROZEN SHUTDOWN OFFSET
If SEPARATE is selected, then the following Functional
Parameter values will be available for use:
PERISHABLE MINIMUM RUN TIME
PERISHABLE MINIMUM OFF TIME
PERISHABLE RESTART TEMPERATURE
PERISHABLE OVERRIDE TEMP
PERISHABLE MAXIMUM OFF TIME
FROZEN MINIMUM RUN TIME
FROZEN MINIMUM OFF TIME
FROZEN RESTART TEMPERATURE
FROZEN OVERRIDE TEMP
FROZEN MAXIMUM OFF TIME
FROZEN SHUTDOWN OFFSET
NOTE
In the event that this Configuration was set
to SEPARATE and the eleven Functional
Parameters for Perishable and Frozen have
been set and the Configuration is changed
from SEPARATE to TOGETHER, the values
from the Perishable settings will be the ones
that will be used.
4.5.2 Stop Parameters
Whenever the unit starts in Start-Stop Operation, it will
remain in the Start-Stop ON cycle until all five of the
following criteria have been satisfied:
1. Unit has run for the selected Minimum Run Time
The MINIMUM RUN TIME is selected in the control
system Functional Parameters. The purpose of this is
to force the unit to run long enough to completely circu-
late the air inside the compartment, and to ensure that
the product temperature is at setpoint. This value may
be set from 4 to 60 minutes in 1 minute intervals. The
factory default setting is 4 minutes.
If all StartStop parameters required to enter a
StartStop Off cycle have been met except this param-
eter, the unit will operate with the compressor and
heaters off and the evaporator fan running until this
parameter has also been met.
2. Engine coolant temperature has warmed
Each time the unit is started in Engine Operation it
must continue to run until the coolant temperature rises
to 95°F (35°C) to ensure it has fully warmed up before
shutdown is allowed.
If all StartStop parameters required to enter a
StartStop Off cycle have been met except this param-
eter, the unit will operate with the compressor and
heaters off and the evaporator fan running until this
parameter has also been met.
3. Battery is fully charged - Voltage
A good battery is defined as having 13.1 VDC at 77°F
(25°C). The control system will calculate the equivalent
voltage based on the ambient temperature and shut-
down will be allowed when battery voltage is at or
above the calculated value.
TIP
The sta tus of th e unit battery can be
checked by reading the Battery Voltage in
the Data List. If “OK.” appears after the volt-
age reading, battery voltage is sufficient to
allow the unit to cycle off.
If in Engine Operation and all Start-Stop parameters
required to enter a Start-Stop Off cycle have been met
except this parameter, the unit will operate with the
compressor and heaters off and the evaporator fan
running until voltage is greater than 13.1 VDC or the
greater of the applicable MINIMUM RUN TIME func-
tional parameter setting, or 20 minutes has elapsed
(this applies to restart based on battery voltage only).

Table of Contents

Other manuals for Carrier TRANSICOLD Vector 8500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier TRANSICOLD Vector 8500 and is the answer not in the manual?

Carrier TRANSICOLD Vector 8500 Specifications

General IconGeneral
BrandCarrier TRANSICOLD
ModelVector 8500
CategoryAutomobile Accessories
LanguageEnglish

Related product manuals