1�- VERIFICATION UPON RECEPTION
Check the following points upon receiving the device:
a) The device meets the specications described in your order.
b) The device has not suffered any damage during transport.
c) Perform an external visual inspection of the device prior to switching it on.
d) Check that it has been delivered with the following:
- An installation guide,
- 4 Retainers used to attach the device,
- 5 plug-in connectors with screws,
- 1 seal,
If any problem is noticed upon reception, immediately contact the transport
company and/or CIRCUTOR's after-sales service.
2�- PRODUCT DESCRIPTION
The CVM-A measures, calculates, displays and records the main electrical parameters and
the quality parameters in single-phase networks, two-phase networks with and without neutral,
balanced three-phase networks, with ARON
(1)
measurement or unbalanced. The measurement
is taken in TRMS, via four AC voltage inputs and four or three current inputs (according to ver-
sion).
There are 2 device models:
CVM-A1000, with a 3.5’’ display.
CVM-A1500, with a 5.6’’ display.
There are 2 versions of the device depending on the current input:
CVM-A1x00-ITF, the current is indirectly measured using /5, /1 A transformers or efcient
MC1 and MC3 series transformers and an input for neutral current measurement.
CVM-A1x00-FLEX, current measurement using Rogowski sensors. As there is no meas-
urement input, the device calculates the neutral current.
(1)
The CVM-A1x00-FLEX version includes an ARON connection.
9
Instruction Manual
CVM-A1000 - CVM-A1500

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor CVM-A1500 and is the answer not in the manual?

Circutor CVM-A1500 Specifications

General IconGeneral
BrandCircutor
ModelCVM-A1500
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals