4�2�2�- EVENT LOGGING
The device records the different events in 3 les:
An *� EVA le, which records all events of the device, from the last time the database
was deleted.
An *�EVQ le, which saves all quality events of the last log.
An *� STD le, which stores the measuring parameters of the last log.
The les can be consulted through the ethernet connection.
4.2.2.1. .EVA le
All events performed by the device are recorded in the �EVA le, with the date and time when
they occurred.
The CVM-A can detect and record the following events:
Table 11: Events of the .EVA le.
Code Description
0 Energy deleted by the user
1 Maximum and minimum values deleted by the user
2 Consumed energy of Tariff 1 deleted by the user
3 Consumed energy of Tariff 2 deleted by the user
4 Consumed energy of Tariff 3 deleted by the user
5 Generated energy of Tariff 1 deleted by the user
6 Generated energy of Tariff 2 deleted by the user
7 Generated energy of Tariff 3 deleted by the user
8 Maximum demand deleted by the user
9 Maximum value of the maximum demand deleted by the user
A
Deletion of maximum values, minimum values, maximum demand and maximum value
of maximum demand
B Event log deletion
C Alarm log deletion
D Energy close deleted by the user
800 Energy deleted due to incorrect CRC
801 Maximum and minimum values deleted due to incorrect CRC
802 Deletion of consumed energy in Tariff 1 due to incorrect CRC
803 Deletion of consumed energy in Tariff 2 due to incorrect CRC
804 Deletion of consumed energy in Tariff 3 due to incorrect CRC
805 Deletion of generated energy in Tariff 1 due to incorrect CRC
806 Deletion of generated energy in Tariff 2 due to incorrect CRC
807 Deletion of generated energy in Tariff 3 due to incorrect CRC
808 Deletion of the maximum demand due to incorrect CRC
809 Deletion of the maximum value of the maximum demand due to incorrect CRC
80B Deletion of the event Logs due to incorrect CRC
80C Deletion of the alarm Logs due to incorrect CRC
80D Deletion of the energy close due to incorrect CRC
1000 Default conguration
1001 Conguration of the transformation ratios
1002 Conguration of the communication parameters
40
CVM-A1000 - CVM-A1500
Instruction Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor CVM-A1500 and is the answer not in the manual?

Circutor CVM-A1500 Specifications

General IconGeneral
BrandCircutor
ModelCVM-A1500
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals