Cisco ASR 9001 AC Electrical Specifications
ValueDescription
Up to two AC power modules per systemPower modules per system
765 VA (volt-amps) per AC power supply (up to two AC power supply
modules per system)
Total AC input power
100–240 VAC nominal (range: 90 to 264 VAC)
220–240 VAC (UK)
Rated input voltage
For each AC power
supply module.
Note
50/60 Hz nominal (range: 47 to 63 Hz)
50/60 Hz (UK)
Rated input line frequency
15 A maximum at 100 VAC
13 A maximum at 220 to 240 VRMS (UK)
Input current rating
15 A North America and Japan; 10 A international; 13 A UKSource AC service requirement
Power redundancy requirements vary, based on system configuration
(number and type of line cards, etc). AC and DC powered systems are
N+1 protected.
Redundancy
DC Electrical Specifications
Cisco ASR 9901 DC Electrical Specifications
ValueDescription
Up to two DC power modules per systemPower modules per system
1600 WTotal DC input power per power
module
–48 VDC nominal in North America
–60 VDC nominal in the European Community
(range: –40.5 to –72 VDC [–75 VDC for 5 ms])
Rated input voltage per power
module
Cisco ASR 9901, ASR 9001, and ASR 9001-S Routers Hardware Installation Guide
144
Technical Specifications
DC Electrical Specifications