SpecificationDescription
2790 VA @ 200 VACMaximum Input VA
2500 W (up to four power supplies)Maximum output power per power supply
35 A (sub cycle duration)Maximum inrush current
8530 BTUMaximum Heat Output
12 ms @ 2500 WMaximum hold up time
12 VDC @ 208 APower supply output voltage
3.3 VDC @ 5APower supply standby voltage
Climate Savers PlatinumEfficiency Rating
20% 50% 100%
90% 94% 91%
Efficiency (80 Plus Platinum Certified)
IEC320 C20Input connector
Table 21: DC-Input Power Supply (UCSB-PSU-2500DC48) Specifications
SpecificationItem
Cisco UCS Software Release 2.0(1)
Capability Catalog Version 42
Minimum software requirement
48 VDC to 60 VDC nominal
(range: -40 VDC to -72 VDC)
DC-input voltage
2500 WMaximum output power
90 A (cold turn-on)Maximum inrush current
71 ACurrent draw at min voltage
40 ACurrent draw at max voltage
2840 WMaximum input VA
88% at 10% load
88% at 20% load
92% at 50% load
88% at 100% load
Efficiency
Cisco UCS 5108 Server Chassis Installation Guide
89
Technical Specifications
Specifications for the Cisco UCS 5108 Blade Server Chassis Power Supply Units

Table of Contents

Other manuals for Cisco UCS 5108

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco UCS 5108 and is the answer not in the manual?

Cisco UCS 5108 Specifications

General IconGeneral
Number of Blade Slots8
I/O Module Bays2
Supported Blade ServersCisco UCS B-Series Blade Servers
Power Supply OptionsUp to four hot-swappable power supplies (AC or DC)
CoolingRedundant hot-swappable fans
ManagementCisco UCS Manager
Blade Slots8
Fabric InterconnectsCisco UCS 6100 or 6200 Series
Power SuppliesUp to 4 hot-pluggable power supplies
Form Factor6RU rack-mountable

Related product manuals