InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
101
FW
Descripti
on
In BTB application many load control and power management functions does not play
active role!
This setpoint is used to adjust the load control type in parallel-to-mains operation.
BASELOA
D
The gen-sets are controlled by their load control loops (i.e. as in SPtM) to
provide constant proportional part of the requested system baseload (see
#SysBaseLoad). The InteliMains does not play active role regarding load
control in parallel-to-mains operation.