8.1.6.1 Configured protections by default
BusL Voltage Unbalance: This protection is by default configured as HistRecOnly with indication
“BusL V unbal”. For more information on this protection see the Protections tab in default
archive.
BusL Current Unbalance: This protection is by default configured as HistRecOnly with indication
“BusL I unbal”. For more information on this protection see the Protections tab in default
archive.
BusR Voltage Unbalance: This protection is by default configured as HistoryRecOnly with indication
“BusR U unbal”. For more information on this protection see the Protections tab in default
archive.
Battery Over and Under Voltage: There are two protections configured by default as Warnings with
indication “Batt volt”. For more information on this protection see the Protections tab in default
archive.
8.1.6.2 Configuration of User configurable protections in GenConfig
It is possible to configure protections on Binary Input, Analog Input or any value that is available in the
controller.
HINT
Since there can be number of protections configured by the user it is possible to prepare more
complex reaction of the Feeder to the state of the voltage on Bus. It is possible to add reaction on over
and under frequency, over and under voltage and other parameters. These protection will be working
along with the fixed protections.
8.1.6.2.1 Binary Input protection configuration
Open I/O tab in GenCofig and adjust parameters that are described below.
Enable/Disable protection for this input
Name of the binary input is also
used as the name of the protection
Type of protection
Toggle normally closed/normally open
Defines when the protection is active
Defines protection delay
8.1.6.2.2 Analog Input protection configuration
Open I/O tab in GenCofig and adjust parameters that are described below.

Table of Contents

Other manuals for ComAp IGS-NT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IGS-NT Series and is the answer not in the manual?

ComAp IGS-NT Series Specifications

General IconGeneral
BrandComAp
ModelIGS-NT Series
CategoryController
LanguageEnglish

Related product manuals