138
12.2.4.4 Setpoint: BinInp delay 3
Group
ComProtSetting
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the delay #3 which can be assigned to an input
configured as alarm input (protection).
NOTE:
Protections configured at a binary inputs can have either fixed 0.5s
evaluation delay or there are three independent delay setpoints and one of
them can be assigned to each particular binary input protection.
12.2.4.5 Setpoint: ForceBlockDel1
Group
ComProtSetting
Range [units]
0.0 .. 60.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay after the binary input Force block 1 has been
deactivated, when the alarms configured as Force block #1 are started to be
evaluated.
12.2.4.6 Setpoint: ForceBlockDel2
Group
ComProtSetting
Range [units]
0.0 .. 60.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay after the binary input Force block 2 has been
deactivated, when the alarms configured as Force block #2 are started to be
evaluated.
12.2.4.7 Setpoint: ForceBlockDel3
Group
ComProtSetting

Table of Contents

Other manuals for ComAp IGS-NT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IGS-NT Series and is the answer not in the manual?

ComAp IGS-NT Series Specifications

General IconGeneral
BrandComAp
ModelIGS-NT Series
CategoryController
LanguageEnglish

Related product manuals