For modem use the COM1 port instead.
12.2.3.6 Setpoint: RS232(1)MBCSpd
Group
Comms settings
Range [units]
9600, 19200, 38400, 57600 [bps]
Related FW
3.0
Description
The setpoint adjusts the communication speed on the COM1 connector when
it is switched to MODBUS or MODBUS-MDM(HW) mode. See also the
setpoint RS232(1) mode.
12.2.3.7 Setpoint: RS232(2)MBCSpd
Group
Comms settings
Range [units]
9600, 19200, 38400, 57600 [bps]
Related FW
3.0
Description
The setpoint adjusts the communication speed on the COM2 connector when
it is switched to MODBUS or MODBUS-MDM(HW) mode. See also the
setpoint RS232(2) mode.
12.2.3.8 Setpoint: RS232(1)MdmIni
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
This setpoint can be used to add extra AT commands at the end of the
initialization sequence of the modem connected to the COM1 port. The
command can be entered with as well as without the "AT" prefix, are
separated with semicolon and maximal length is 31 characters.
The setpoint can't be modified via the IG-NT built-in terminal.
12.2.3.9 Setpoint: RS232(2)MdmIni
Group
Comms settings

Table of Contents

Other manuals for ComAp IGS-NT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IGS-NT Series and is the answer not in the manual?

ComAp IGS-NT Series Specifications

General IconGeneral
BrandComAp
ModelIGS-NT Series
CategoryController
LanguageEnglish

Related product manuals