InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013
12.2.8.26 Setpoint: #MinRunPower 1
This setpoint is used to adjust certain minimum value of the sum of nominal
power of all running gen-sets. If the function is active, then the gen-sets
would not be stopped, although the reserve for stop is fulfiled, if the total
remaining nominal power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated
by the input MinRun power 1 which is in MINT application (in InteliMains it is
for compatibility purposes only).
NOTE:
When more than one binary input MinRunPower is activated then
MinRunPower with the highest number is active.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.27 Setpoint: #MinRunPower 2
This setpoint is used to adjust certain minimum value of the sum of nominal
power of all running gen-sets. If the function is active, then the gen-sets
would not be stopped, although the reserve for stop is fulfiled, if the total
remaining nominal power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated
by the input MinRun power 2 which is in MINT application (in InteliMains it is
for compatibility purposes only).
NOTE:
When more than one binary input MinRunPower is activated then
MinRunPower with the highest number is active.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.