Loading...
IGS-NT Installation Guide
122
SG COM
SG OUT
VoutR
0V
5V
Cummins
ONAN
Sync/Load ctrl:
Speed gov bias = 2,50 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0V
SpeedGovHiLim = 5V
SG COM
SG OUT
VoutR
20
11
Cummins
QST30
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
POSITIVE
SG COM
SG OUT
Vout
32
CUMMINS
QSL9
9
Sync/Load ctrl:
Speed gov bias = 3,50 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 2,5V
SpeedGovHiLim = 5V
03-11
SG COM
SG OUT
VoutR
03-12
CUMMINS
GCS
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 2,5V
SpeedGovHiLim = 7,5V
Barber Colman
SG COM
SG OUT
VoutR
2
9
Barber Colman
DYNA 8000
Sync/Load ctrl:
Speed gov bias = 6,00 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 4V
SpeedGovHiLim = 8V
SG COM
SG OUT
VoutR
2
Barber Colman
DYN1 10684
9
Sync/Load ctrl:
Speed gov bias = 6,00 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 4V
SpeedGovHiLim = 8V
GAC
SG COM
SG OUT
VoutR
G
N
GAC
ESD 5500
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
NEGATIVE
SpeedGovLowLim = 4V
SpeedGovHiLim = 6V

Table of Contents

Related product manuals