InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
191
Learn more about load shedding in the separate chapter Load shedding.
12.2.12.4 Setpoint: Ld recon del
Group
Load shedding
Range [units]
0 .. 600 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used to adjust time period the percentage of the power
transferred through BTB must be below the Ld recon level limit to allow
reconnection of next load group.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
12.2.12.5 Setpoint: AutoLd recon
Group
Engine Protect
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint selects whether the reconnection of the load occurs
automatically when the power transferred through BTB stays below the
reconnection limit for a period of the reconnection delay or the reconnection
must be initiated manually by the input ManualLdRecon.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
12.2.13 Group: Timer settings
12.2.13.1 Setpoint: Timer channel 1
Group
Timer settings

Table of Contents

Other manuals for ComAp IGS-NT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IGS-NT Series and is the answer not in the manual?

ComAp IGS-NT Series Specifications

General IconGeneral
BrandComAp
ModelIGS-NT Series
CategoryController
LanguageEnglish

Related product manuals