ID–Lite-2.0 User guide, ©ComAp January 2011 34
ID-Lite-2.0 User guide.pdf
Battery
-
ID-Lite
4k7
+
-
Power
Supply
2x
470
COM
- POWER
AI1
AI2
AI3
Mixed connection of ID-Lite analog inputs:
AI1 binary input
AI2 three state input
AI3 analog resistive input
Analog inputs are designed for resistive sensors with resistance in range of 0 to 2,4k.
To ensure a proper function use shielded cables, especially for length over >3m.
Current output transducers
InteliDrive-Lite analog inputs are mainly designed for resistor sensors.
In special case transducers to 4-20mA output can be used for oil measuring (10.0Bar or 6.0Bar). Use
predefined 4-20mA/100 or 4-20mA/60 sensors.
This method reduces the input resolution by less than 50%. Some types of transducers are not
suitable for connection to ID-Lite analog inputs because of influencing by ID-Lite analog input.
As binary input
Open, close state are detected, threshold level is 750 .
As three state input
Open, close and failure state are detected. Threshold level is 750 , failure is detected when circuit
resistance is <10 or > 2400 .
Unused analog inputs
Configure Type = Not used
Binary inputs