ID–Lite-2.0 User guide, ©ComAp – January 2011                                                   34 
ID-Lite-2.0 User guide.pdf 
4k7 
+
-
Power
Supply
2x
470
COM
- POWER
AI1
AI2
AI3
 
 
Mixed connection of ID-Lite analog inputs: 
 
AI1 – binary input 
AI2 – three state input 
AI3 – analog resistive input 
 
Analog inputs are designed for resistive sensors with resistance in range of 0Ω to 2,4kΩ. 
To ensure a proper function use shielded cables, especially for length over >3m. 
Current output transducers 
InteliDrive-Lite analog inputs are mainly designed for resistor sensors.  
In special case transducers to 4-20mA output can be used for oil measuring (10.0Bar or 6.0Bar). Use 
predefined 4-20mA/100 or 4-20mA/60 sensors.  
This method reduces the input resolution by less than 50%. Some types of transducers are not 
suitable for connection to ID-Lite analog inputs because of influencing by ID-Lite analog input.  
As binary input 
Open, close state are detected, threshold level is 750 Ω. 
As three state input 
Open, close and failure state are detected.  Threshold level is 750 Ω, failure is detected when circuit 
resistance is <10 Ω  or > 2400 Ω. 
Unused analog inputs 
Configure   Type = Not used 
 
Binary inputs