ID–Lite-2.0 User guide, ©ComAp – January 2011                                                   46 
ID-Lite-2.0 User guide.pdf 
Inputs and outputs 
Hint: 
Any Binary input or output can be configured to any ID-Lite controller terminal or changed to different 
function by LiteEdit (3.0 or higher) software. There is fix 1 sec delay when any binary input is 
configured as protection. 
 
Binary inputs ID-Lite - default 
BI1  Rem start/stop 
BI2  Access lock 
BI3  Emergency stop  
BI4  Remote OFF 
BI5  Sprinkler 
BI6  RemControlLock 
Binary inputs – list 
Not used 
Binary input has no function. Use this configuration when Binary input is not connected. 
Alarm  
If the input is closed (or opened) selected alarm is activated.   
Binary Alarm configuration items 
Name    14 characters ASCII string 
NC  Normally closed Contact type 
NO  Normally opened 
Warning   Alarm type 
Shut down   
All the time   Alarm active 
Engine running only   
Rem start/stop  
External request for engine run. AUT mode only. 
Emergency stop 
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default 
configuration. 
 
Hint: 
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured. To 
back-up the Emergency stop function it is recommended to connect separate circuit for disconnection 
of Fuel solenoid and Starter signals. 
Sprinkler 
If the input is closed all alarms are disabled except the binary input EMERGENCY STOP and "engine 
overspeed protection".