ID–Lite-2.0 User guide, ©ComAp – January 2011                                                   68 
ID-Lite-2.0 User guide.pdf 
Step:   1 
Range:   0 – 10000 
Default:  100 
LoadDnLimit  [ - ] 
Load limit regulator PI output low limit. 
Step:   1 
Range:   0 – 10000 
Default:  9900 
Load Gain  [ % ] 
Regulator gain. 
Step:   0,1 
Range:   -200,0% – +200,0% 
Default:  0 
Load Integral  [ % ] 
Regulator integration factor. 
Step:   0,1 
Range:   0% – +100,0% 
Default:  0 
Load CMP Input  [ RPM, ECU:Load,   
CU: IA1, CU: AI2, CU: AI3, AIO: IA1, AIO: AI2, AIO: AI3, AIO: AI4 ] 
Comparator with hysteresis analog input selection or from central unit (CU) or from plug-in (AIO). 
Load CMP Off 
Limit to close LBO LoadSwitch 
Step:   1 
Range:   -10000 – +10000 
Load CMP On 
Limit to open LBO LoadSwitch 
Step:   1 
Range:   -10000 – +10000 
Engine protect 
Eng prot del  [s] 
During the start of the engine, some engine protections have to be blocked (e.g. Oil pressure). 
The protections are unblocked after the Protection del time. The time starts after reaching Start RPM. 
Step:   1s 
Range:   0 – 300 s 
BIN6 delay  [s] 
Specific protection delay adjustable on Binary Input 6. Delay is active for Wrn or Sd protection only - 
not for functions like Rem Start/Stop. Protection delay is active for both Binary input NO / NC 
configuration. BIN6 del starts after Eng prot del when BI6 protection is configured “Running only”. 
Step:   1s 
Range:   0 – 300 s