ID–Lite-2.0 User guide, ©ComAp – January 2011                                                   65 
ID-Lite-2.0 User guide.pdf 
Regulator 
LBI Speed Up
LBI Speed Down
AOUT
OutChar
InpChar
 
 
LAI SpdRequest  [ OFF, CU:AI1, CU:AI2, CU:AI3  
AIO: IA1, AIO: AI2, AIO: AI3, AIO: AI4 ] 
Selection of analog Speed request in controller MAN mode.  
OFF: Speed request selection is done by binary inputs. 
CU: AI1, CU: AI2, CU: AI3: AIO1 … AIO4:  Speed request via analog input only. Binary inputs are 
ignored. Analog speed request is ignored in AUT mode. 
Reg Input  [CU: AI1, CU: AI2, CU: AI3,   
AIO: IA1, AIO: AI2, AIO: AI3, AIO: AI4, RPM-BI3 ] 
PI loop analog input selection or from central unit (CU) or from plug-in (AIO).  The Speed request 
(regulator output) is set to Reg Bias value in the case of selected analog input sensor fail. 
Reg Bias  [ - ] 
Constant PI regulator output when the LBI R Reg Disable = closed.  
Step:   1 
Range:   0 – 10000 
Default:  0 
 
Request 1  [ - ] 
Regulator requested value. 
Step:   1 
Range:   -10000 – +10000 
Default:  0 
Request 2  [ - ] 
Regulator requested value when LBI Request2 is active. 
Step:   1 
Range:   -10000 – +10000 
Default:  0 
Reg Gain  [ % ] 
Regulator gain. 
Step:   0,1