Preglow time  [s] 
Time of the PREGLOW output closed prior to the engine start. Set to zero if you want to leave the 
output PREGLOW opened.  
 
Function with shorter period (Prestart time or Preglow time) starts later to finish both in the same time 
– when Starting RPM speed is reached. 
Step:   1s 
Range:   0 – 600 s 
MaxCrank time  [s] 
Maximum time limit of engine cranking.  
Step:   1s 
Range:   1 – 60 s 
CrnkFail pause  [s] 
Pause between crank (engine start) attempts.  
Step:   1s 
Range:   5 – 60 s 
Crank attemps  [-] 
Max number of crank (engine start) attempts.  
Step:   1 
Range:   1 – 10 
Idle time   [s] 
Idle time delay starts when RPM exceeds Start RPM. Start fail is detected when during Idle state RPM 
decreases below 2.  
During the Idle time timer running the binary output IDLE/NOMINAL is opened, when it elapses the 
IDLE/NOMINAL output closes.  Binary output IDLE/NOMINAL opens during Cooling period again. 
Engine can be switched between Idle and Running state by Binary input Nominal/Idle in MAN mode. 
Step:   1 s 
Range:   0 – 600 s 
 
 
Idle speed    [ RPM ] 
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by 
Binary input Nominal/Idle and after Engine shut-down.  
Step:   1RPM 
Range:   Starting RPM – MinSpeedLimit 
 
Cooling speed [ NOMINAL, IDLE ] 
Selects the function of the Binary output  IDLE/NOMINAL during engine Cooling state.  
NOMINAL :  Cooling is executed at Nominal speed. 
IDLE:   Cooling is executed at Idle speed. 
Hint: