InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
42
O10
Choke
The output is activated while engine is cranking and between cranking attempts. Choke Time (timer)
will start on engine rune. The Choke output will close when Choke Time elapsed.
Prestart Time
0 - 600 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Gen-set start failed
Starter Output
On
Off
TimeStart
Choke Output
On
Prestart Time
0 - 600 s
Maximum
Cranking Time
0 - 60 s
On
Off
Time
Start
Engine run
Max. Stab. Time 7 sMin. Stab. Time
Starter Output
Stop
Choke Time
Choke Output