InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
43
O11
Glow Plugs
This output is activated before each cranking procedure for Prestart Time but maximally for 8s!
Prestart Time
8 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Cranging Fail
Pause 8 s
Gen-set start failed
On
Off
Starter Output
TimeStart
Glow Plugs
Output On
Prestart Time
> 8 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Cranging Fail
Pause 8 s
Gen-set start
failed
On
Off
TimeStart
Glow Plugs
Output On
8 s
Starter Output
Prestart Time
> 8 s
Maximum
Cranking Time
0 - 60 s
Gen-set start failed shutdown,
if the voltage or frequency are not in
the limit
On
Off
TimeStart
Engine run
Max. Stab. Time 7 sMin. Stab. Time
Starter Output
8 s
Glow Plugs
Output On