Name of test Procedure Notes
External Power supply EN 61000-4-11
Power supply variation EN 61000-4-11
Low temperature EN 60068-2-1, Ab, Ad -2C/ 16h
Cyclic damp heat test EN 60068-2-30, Db
Dry heat EN 60068-2-2, Ab, Ad 70°C/ 16h
Sinusoidal vibration EN 60068-2-6 test Fc 5Hz - 25Hz/ ±1,6mm; 25Hz - 100Hz / 4g
Flammability EN 60695-11-5:05
High Voltage
Germanische Lloyd spec.,
VI-Part 7, §14
Power supply terminals against box: Uef. 572 V;
duration 1 min
Insulation resistance
Germanische Lloyd spec.,
VI-Part 7, §13
Electrostatic discharge EN 61000-4-2 6kV contact discharge; 8kV air discharge
Radiated elmag. field
immunity
EN 61000-4-3
Fast low energy
transients/bursts
EN 61000-4-4
Slow high energy
transient/surges
EN 61000-4-5