Indoor Unit (RA Models) SiEBE18-526
90 Function
7.10 Inverter POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Details of the
Control
When POWERFUL button is pushed in each operation mode, the fan speed / setting
temperature will be converted to the following states in a period of twenty minutes.
In case of FTXS20-35D, CTXS50D
Ex.) : Powerful operation in cooling mode.
Operation mode Fan speed Target set temperature
COOL H tap + 50 rpm 18°C
DRY Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –2°C
HEAT H tap + 50 rpm 30°C
FAN H tap + 50 rpm
AUTO Same as cooling /
heating in Powerful
operation
The target is kept
unchanged
(R4560)
Target temp.
Fan
50rpm
Set temp.
18°C
Powerful ON
Powerful OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote control.
20min.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. Powerful operation is OFF.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus D-Series and is the answer not in the manual?

Daikin Super Multi Plus D-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus D-Series
CategoryHeat Pump
LanguageEnglish

Related product manuals