SiEBE18-526 Protection Control
Function 67
4. Protection Control
4.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
In cooling operation
Pc
>
3.6MPaEvery 10 sec.
Pc
>
3.55MPa
Pc
<
3.45MPa
Pc>3.75MPa
Keeping the current step
Every 60 sec.
3.45MPa
<
Pc3.55MPa
or
&
High pressure not limited
High pressure limited
INV upper limit frequency:
1-step up from current
compressor frequency
INV upper limit frequency:
1-step up from current
compressor frequency
Pc: HP pressure sensor detection value
INV upper limit frequency :
1-step down from current
compressor frequency
When occurring 3 times within 30
minutes, HPS is activated without high
pressure standby, thus outputting the
malfunction code "E3".
(Q0374)
INV upper limit frequency
Pc 3.55MPa
During oil return operation
After oil return operation
Stopping operation
Heating operation
Every
5 min.
High pressure
standby

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus D-Series and is the answer not in the manual?

Daikin Super Multi Plus D-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus D-Series
CategoryHeat Pump
LanguageEnglish

Related product manuals