SiEBE18-526 List of Malfunction Code
Troubleshooting 255
3. List of Malfunction Code
9: Blink 8: ON 7: OFF
Malfunction
code
Malfunction contents Page Referred
RA Indoor
Unit
SkyAir
Indoor Unit
BP Unit Outdoor
Unit
Indoor
Unit
A0 Error of external protection device
A1 PC board defect, E
2
PROM defect 257 268
A3 Malfunction of drain level control system (33H) 269
A5 Freeze-up protection or high pressure control 258
A6 Fan motor (MF) lock, overload 260, 261 272, 273
A7 Malfunction of swing flap motor (MA) 275
A9 Malfunction of electronic expansion valve (20E) 287
AF Drain pump error 271
AJ Malfunction of capacity setting 277
C4 Malfunction of thermistor (R2T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
263 278
C5 Malfunction of thermistor (R3T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
279
C7 Shutter drive motor / shutter limit switch abnormality 264
C9 Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
263 280
CA Malfunction of thermistor for air outlet (loose
connection, disconnection, short circuit, failure)
————
CJ Malfunction of thermostat sensor in remote controller 281
Outdoor
Unit
E1 PC board defect, E
2
PROM defect 294
E2 Faulty BP unit PCB 288
E3 Actuation of high pressure switch 295
E4 Actuation of low pressure switch 296
E5 Compressor motor lock 297
E6 Standard compressor lock or over current
E7 Malfunction of outdoor unit fan motor 298
E9 Malfunction of moving part of electronic expansion
valve (Y1E~2E)
———299
F3 Abnormal discharge pipe temperature 300
F6 Refrigerant overcharged
H3 Malfunction of high pressure switch
H4 Actuation of low pressure switch
H7 Abnormal outdoor fan motor signal
H9 Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
———301
J0 Faulty BP liquid or gas pipe thermistor 289
J2 Current sensor malfunction
J3 Malfunction of discharge pipe thermistor (R3T) (loose
connection, disconnection, short circuit, failure)
———302
J5 Malfunction of thermistor (R2T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
———303
J6 Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
———304
J7 Malfunction of header thermistor
J8 Malfunction of thermistor (R7T) for oil equalizing pipe.
(loose connection, disconnection, short circuit,
failure)
————
J9 Malfunction of receiver gas pipe thermistor (R5T) 305
JA Malfunction of discharge pipe pressure sensor 306
JC Malfunction of suction pipe pressure sensor 307
L0 Inverter system error

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus D-Series and is the answer not in the manual?

Daikin Super Multi Plus D-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus D-Series
CategoryHeat Pump
LanguageEnglish

Related product manuals