SiEBE18-526 Instruction
System Configuration 143
2. Instruction
2.1 RMXS Series
REGARDING USE
S
uper Multi Plus System air conditioner
POINTS THE CUSTOMER SHOULD BE AWARE OF
COMFORT
At startup
After the power is initially turned on, it will take approx. 10 minutes until startup. Usually the unit will start
in 5 minutes.
At startup of heating operation
The colder it is outside or the greater the number of indoor units, the longer the time required from the
start of operation until the emission of warm air (around 35°C). When the outside temperature is -5 to
2°C, the inside temperature is 5 to 10°C, and total indoor unit combination is 100% capacity, the first
startup of all indoor units in the morning will take approximately 20 to 30 minutes.
Oil return operation will be performed once every 8 hours to preserve the lubrication of oil to the
compressor.
Since operation is switched to cooling cycle during heating operation in order to return the oil, heating
operation will not be possible for around 5 to 10 minutes.
Heating operation
When the outside temperature is 28°C or higher, the unit will be set to the standby mode for protection.
OPERATING NOISE
At startup
During startup, in order to emit warm or cool air as quickly as possible, the sound of refrigerant flowing
will be heard for a short time (1 to 2 minutes) from the outdoor unit.
At shutdown
In order to ensure smooth startup the next time this unit is operated, the outdoor unit will continue to
operate for around 2 to 5 minutes after shutdown. (The time of continued operation depends on the
outside temperature, capacity of connected indoor units, and connection pipe length.)
Defrost
When the outside unit is performing defrosting operation, the fan of the indoor unit will stop temporarily,
and the slight sound of refrigerant flowing will be heard.
Cooling at low outside temperatures
During cooling operation when the outside temperature is 20°C or less, the fan of the outdoor unit will
operate at low speed to preserve capacity and the outdoor unit valve will be opened depending on the
pressure conditions, making it more likely that the sound of refrigerant flowing will be heard.
Excessive heating load
During heating operation when the outside temperature is high (15 to 24°C), the fan of the outdoor unit
will be operated at low speed, making it more likely that the sound of refrigerant flowing will be heard from
the outdoor unit.
3PN00286-13U

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus D-Series and is the answer not in the manual?

Daikin Super Multi Plus D-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus D-Series
CategoryHeat Pump
LanguageEnglish

Related product manuals