Other Control SiEBE18-526
74 Function
5. Other Control
5.1 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adaptor is required.
[Demand 1 setting]
[Demand 2 setting]
H Other protection control functions have precedence over the above operation.
5.2 Heating Operation Prohibition
Heating operation is prohibited above 30°CDB outdoor air temperature.
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%
Setting Standard for upper limit of power consumption
Demand 2 setting 1 Approx. 30%
Demand 2 setting 2 (factory setting) Approx. 40%
Demand 2 setting 3 Approx. 50%