Special Control SiEBE18-526
66 Function
3.6 Stopping Operation
3.6.1 When System is in Stop Mode
3.7 Pressure Equalization Prior to Startup
Before activating the compressor, the activation load is lightened by equalization across the
compressor. In addition, inverters turn on electricity and capacitors are charged.
Actuator Operation
Compressor OFF
Outdoor unit fan OFF
Four way valve Keep former condition.
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve (EV2) 0 pls
Hot gas bypass valve (SVP)
OFF
Receiver gas discharging valve (SVG) OFF
Ending conditions Indoor unit thermostat is turned ON.
Actuator Operation Remarks
Compressor OFF
Outdoor unit fan
Cooling: STEP7
Heating: Ta>26°C; STEP8,
Ta26°C; OFF
Four way valve Keep former condition.
Main electronic expansion valve
(EV1)
0 pls
Subcooling electronic expansion
valve (EV2)
0 pls
Hot gas bypass valve (SVP) ON
Receiver gas discharging valve
(SVG)
OFF
Ending conditions
3 min.
Pc-Pe<0.2 MPa
or

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus D-Series and is the answer not in the manual?

Daikin Super Multi Plus D-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus D-Series
CategoryHeat Pump
LanguageEnglish

Related product manuals