Indoor Unit (SkyAir Models) SiEBE18-526
100 Function
Using Conditions
for Remote
Controller
Thermostat
(Applicable models: FHQ & FFQ only)
Remote controller thermostat is equipped only in wired remote controller.
Even when “ use remote controller thermostat ” is selected in service mode, the remote
controller thermostat may not be used.
< Conditions not to use >
1. When the remote controller thermostat malfunctions.
2. When the one remote controller group control is applied.
( Excluding simultaneous ON/OFF operation )
3. When conditions relating set temperature with remote controller and suction air temperature
are out of the operating zone of remote controller thermostat shown in below diagram.
( Excluding when automatic operation mode is selected. Whenever operation is in the
automatic mode, remote controller thermostat can be used. )
ts: Set temp. (°C)
For cooling
ts =
th + 3
ts = th + 1
ts = th - 1
ts = th - 3
Th: Suction air temp. (°C)
Differential zone
Remote control thermostat
operating zone
(S1118)
35
23
21
20
21 2335
20
ts: Set temp. (°C)
For heating
ts = th + 1
ts = th - 1
ts = th - 10
ts = th - 12
Th: Suction air temp. (°C)
Differential zone
Remote control thermostat
operating zone
(S2746)
30
28
18
16
15
15
27 30
29