SiEBE18-526 Troubleshooting for Outdoor Unit
Troubleshooting 313
Troubleshooting
(Q0439)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The
transmission
wiring between the
outdoor unit PCB
inverter unit is
disconnected.
YES
Fix the disconnection and turn on
again.
Connect transmission wiring and
turn on again.
NO
YES
The voltage
between red and
white of X1A on the inverter
unit is the power supply
voltage.
Check the noise filter (Z1F) for
disconnection, and check the
power supply wiring or the inverter
PCB.
Replace inverter PCB.
When the LC malfunction occur
again, replace control PCB.
NO
NO
YES
NO
Are the
connectors
between the main
PC board (A1P) and
inverter PCB
(A2P) connected
securely?
The
microcomputer
monitor (green) on
the inverter PCB
isblinking.
Defect of outdoor main PCB or
defect of inverter PCB.
YES

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus D-Series and is the answer not in the manual?

Daikin Super Multi Plus D-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus D-Series
CategoryHeat Pump
LanguageEnglish

Related product manuals