3.26 Parameters 30-** Special Features
3.26.1 30-2* Adv. Start Adjust
30-22 Locked Rotor Detection
Turn the locked rotor detection on or o. Available only for PM
motors in VVC
+
.
Option: Function:
[0] O
[1] On Protects the motor from the locked-rotor condition. The
control algorithm detects a possible locked-rotor
condition in the motor and trips the frequency
converter to protect the motor.
30-23 Locked Rotor Detection Time [s]
Range: Function:
Size related* [0.05 - 1 s] Enter the time period for detecting
the locked-rotor condition. A low
parameter value provides faster
detection.
3.26.2 30-8* Compatibility
30-81 Brake Resistor (ohm)
Range: Function:
50.
Ohm*
[5. -
32000.0
Ohm]
Set the brake resistor value in Ω with 2
decimals. This value is used for
monitoring the power to the brake
resistor in parameter 2-13 Brake Power
Monitoring.
3.26.3 30-9* Wi LCP
Parameters for conguring the wireless LCP 103.
30-90 SSID
Range: Function:
Size
related*
[1 -
32 ]
Enter the wireless network name (SSID). The
default value is: Danfoss_<Serial number of
the frequency converter>. The serial number
is in parameter 15-51 Frequency Converter
Serial Number.
30-91 Channel
Range: Function:
5* [1 -
11 ]
Enter the wireless channel number. The default
channel number is 5. Change the channel number,
if there is an interference from other wireless
networks. Recommended channels:
USA territory: 1, 6, 11.
Europe: 1, 7, 13.
30-92 Password
Range: Function:
Size related* [8 - 48 ] Enter the wireless network password.
Password length: 8–48 characters.
30-97 Wi Timeout Action
Select which action to execute if a local reference (hand-on
mode) or a remote reference (auto-on mode) is set via the
wireless connection and the connection is lost.
Option: Function:
[0] * Do Nothing The frequency converter does
not do any extra actions.
[1] Stop Motor The frequency converter
stops the motor (if the motor
was started via a wireless
connection).
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 243