3.26 Parameters 30-** Special Features
3.26.1 30-2* Adv. Start Adjust
30-22 Locked Rotor Detection
Turn the locked rotor detection on or o. Available only for PM
motors in VVC
+
.
Option: Function:
[0] O
[1] On Protects the motor from the locked-rotor condition. The
control algorithm detects a possible locked-rotor
condition in the motor and trips the frequency
converter to protect the motor.
30-23 Locked Rotor Detection Time [s]
Range: Function:
Size related* [0.05 - 1 s] Enter the time period for detecting
the locked-rotor condition. A low
parameter value provides faster
detection.
3.26.2 30-8* Compatibility
30-81 Brake Resistor (ohm)
Range: Function:
50.
Ohm*
[5. -
32000.0
Ohm]
Set the brake resistor value in Ω with 2
decimals. This value is used for
monitoring the power to the brake
resistor in parameter 2-13 Brake Power
Monitoring.
3.26.3 30-9* Wi LCP
Parameters for conguring the wireless LCP 103.
30-90 SSID
Range: Function:
Size
related*
[1 -
32 ]
Enter the wireless network name (SSID). The
default value is: Danfoss_<Serial number of
the frequency converter>. The serial number
is in parameter 15-51 Frequency Converter
Serial Number.
30-91 Channel
Range: Function:
5* [1 -
11 ]
Enter the wireless channel number. The default
channel number is 5. Change the channel number,
if there is an interference from other wireless
networks. Recommended channels:
USA territory: 1, 6, 11.
Europe: 1, 7, 13.
30-92 Password
Range: Function:
Size related* [8 - 48 ] Enter the wireless network password.
Password length: 8–48 characters.
30-97 Wi Timeout Action
Select which action to execute if a local reference (hand-on
mode) or a remote reference (auto-on mode) is set via the
wireless connection and the connection is lost.
Option: Function:
[0] * Do Nothing The frequency converter does
not do any extra actions.
[1] Stop Motor The frequency converter
stops the motor (if the motor
was started via a wireless
connection).
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 243
3 3

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals