EasyManua.ls Logo

Danfoss VLT AQUA Drive FC 202

Danfoss VLT AQUA Drive FC 202
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.1.17 20-** Drive Closed Loop
Param-
eter #
Parameter description Default value 4 set-up Change during
operation
Conversion
index
Type
20-0* Feedback
20-00 Feedback 1 Source [2] Analog Input 54 All set-ups TRUE - Uint8
20-01 Feedback 1 Conversion [0] Linear All set-ups FALSE - Uint8
20-02 Feedback 1 Source Unit ExpressionLimit All set-ups TRUE - Uint8
20-03 Feedback 2 Source [0] No function All set-ups TRUE - Uint8
20-04 Feedback 2 Conversion [0] Linear All set-ups FALSE - Uint8
20-05 Feedback 2 Source Unit ExpressionLimit All set-ups TRUE - Uint8
20-06 Feedback 3 Source [0] No function All set-ups TRUE - Uint8
20-07 Feedback 3 Conversion [0] Linear All set-ups FALSE - Uint8
20-08 Feedback 3 Source Unit ExpressionLimit All set-ups TRUE - Uint8
20-12 Reference/Feedback Unit ExpressionLimit All set-ups TRUE - Uint8
20-2* Feedback/Setpoint
20-20 Feedback Function [4] Maximum All set-ups TRUE - Uint8
20-21 Setpoint 1 0 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-22 Setpoint 2 0 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-23 Setpoint 3 0 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-6* Sensorless
20-60 Sensorless Unit ExpressionLimit All set-ups TRUE - Uint8
20-69 Sensorless Information 0 N/A All set-ups TRUE 0 VisStr[25]
20-7* PID Autotuning
20-70 Closed Loop Type [0] Auto 2 set-ups TRUE - Uint8
20-71 PID Performance [0] Normal 2 set-ups TRUE - Uint8
20-72 PID Output Change 0.10 N/A 2 set-ups TRUE -2 Uint16
20-73 Minimum Feedback Level
-999999
ProcessCtrlUnit 2 set-ups TRUE -3 Int32
20-74 Maximum Feedback Level
999999
ProcessCtrlUnit 2 set-ups TRUE -3 Int32
20-79 PID Autotuning [0] Disabled All set-ups TRUE - Uint8
20-8* PID Basic Settings
20-81 PID Normal/ Inverse Control [0] Normal All set-ups TRUE - Uint8
20-82 PID Start Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
20-83 PID Start Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
20-84 On Reference Bandwidth 5% All set-ups TRUE 0 Uint8
20-9* PID Controller
20-91 PID Anti Windup [1] On All set-ups TRUE - Uint8
20-93 PID Proportional Gain 2 N/A All set-ups TRUE -2 Uint16
20-94 PID Integral Time 8 s All set-ups TRUE -2 Uint32
20-95 PID Dierentiation Time 0 s All set-ups TRUE -2 Uint16
20-96 PID Di. Gain Limit 5 N/A All set-ups TRUE -1 Uint16
Parameter Lists
VLT
®
AQUA Drive FC 202
270 Danfoss A/S © 05/2018 All rights reserved. MG20OB02
44

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Related product manuals