3.14 Parameters 15-** Drive Information
Parameter group containing frequency converter
information such as operating data, hardware congu-
ration, and software versions.
3.14.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is
turned o.
15-01 Running Hours
Range: Function:
0 h* [0 -
2147483647 h]
View how many hours the motor has run.
Reset the counter in
parameter 15-07 Reset Running Hours
Counter. The value is saved when the
frequency converter is turned o.
15-02 kWh Counter
Range: Function:
0 kWh* [0 -
2147483647
kWh]
Register the power consumption of
the motor as an average value over 1
hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0* [0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
temperature faults.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
overvoltages.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset No reset of the kWh counter is required.
[1] Reset counter Press [OK] to reset the kWh counter to 0
(see parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not
reset
No reset of the running hours counter is
required.
[1] Reset
counter
Select [1] Reset counter and press [OK] to reset
the running hours counter
(parameter 15-01 Running Hours) and
parameter 15-08 Number of Starts to 0 (see
also parameter 15-01 Running Hours).
15-08 Number of Starts
Range: Function:
0* [0 -
2147483647 ]
NOTICE
This parameter is reset when resetting
parameter 15-07 Reset Running Hours
Counter.
This is a readout parameter only. The
counter shows the number of starts and
stops caused by a normal start/stop
command and/or when entering/leaving
sleep mode.
3.14.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (parameter 15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(parameter 15-12 Trigger Event) and window
(parameter 15-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
[0] * None
[1472] VLT Alarm Word
[1473] VLT Warning Word
[1474] VLT Ext. Status Word
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1622] Torque [%]
[1625] Torque [Nm] High
[1630] DC Link Voltage
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 141