3-17 Reference Resource 3
[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] Lcp Potentiometer
3-18 Relative Scaling Ref. Resource
*[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] Lcp Potentiometer
3-4* Ramp 1
3-40 Ramp 1 Type
*[0] Linear
[2] Sine2 ramp
3-41 Ramp 1 Ramp up Time
0.05 - 3600 s * 3.00 s
3-42 Ramp 1 Ramp Down Time
0.05 - 3600 s * 3.00 s
3-5* Ramp 2
3-50 Ramp 2 Type
*[0] Linear
[2] Sine2 ramp
3-51 Ramp 2 Ramp up Time
0.05 - 3600 s * 3.00 s
3-52 Ramp 2 Ramp down Time
0.05 - 3600 s * 3.00 s
3-8* Other Ramps
3-80 Jog Ramp Time
0.05 - 3600 s * 3.00 s
3-81 Quick Stop Ramp Time
0.05 - 3600 s * 3.00 s
4-** Limits / Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
[0] Clockwise
[1] CounterClockwise
*[2] Both
4-12 Motor Speed Low Limit [Hz]
0.0 - 400.0 Hz * 0.0 Hz
4-14 Motor Speed High Limit [Hz]
0.1 - 400.0 Hz * 65.0 Hz
4-16 Torque Limit Motor Mode
0 - 400 % * 150 %
4-17 Torque Limit Generator Mode
0 - 400 % * 100 %
4-5* Adj. Warnings
4-50 Warning Current Low
0.00 - 26.00 A * 0.00 A
4-51 Warning Current High
0.00 - 26.00 A * 26.00 A
4-58 Missing Motor Phase Function
[0] Off
*[1] On
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0.0 - 400.0 Hz * 0.0 Hz
4-63 Bypass Speed To [Hz]
0.0 - 400.0 Hz * 0.0 Hz
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
[0] No function
[1] Reset
[2] Coast inverse
[3] Coast and reset inv.
[4] Quick stop inverse
[5] DC-brake inv.
[6] Stop inv
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[12] Enable start forward
[13] Enable start reverse
[14] Jog
[16-18] Preset ref bit 0-2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Setup select bit 0
[28] Catch up
[29] Slow down
[34] Ramp bit 0
[60] Counter A (up)
[61] Counter A (down)
[62] Reset counter A
[63] Counter B (up)
[64] Counter B (down)
[65] ResetCounter B
5-11 Terminal 19 Digital Input
See par. 5-10. * [10] Reversing
5-12 Terminal 27 Digital Input
See par. 5-10. * [1] Reset
5-13 Terminal 29 Digital Input
See par. 5-10. * [14] Jog
5-15 Terminal 33 Digital Input
See par. 5-10. * [16] Preset ref bit 0
[26] Precise Stop Inverse
[27] Start, Precise Stop
[32] Pulse Input
5-4* Relays
5-40 Function Relay
*[0] No opreation
[1] Control ready
[2] Drive ready
[3] Drive ready, Remote
[4] Enable / No warning
[5] Drive running
[6] Running / No warning
[7] Run in range / No warning
[8] Run on ref / No warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[21] Thermal warning
[22] Ready, No thermal warning
[23] Remote ready, No thermal warning
[24] Ready, Voltage ok
[25] Reverse
[26] Bus ok
[28] Brake,NoWarn
[29] Brake ready/NoFault
[30] BrakeFault (IGBT)
[32] Mech.brake control
[36] Control word bit 11
[51] Local ref. active
[52] Remote ref. active
[53] No alarm
[54] Start cmd active
[55] Running reverse
[56] Drive in hand mode
[57] Drive in auto mode
[60-63] Comparator 0-3
[70-73] Logic rule 0-3
[81] SL digital output B
5-5* Pulse Input
5-55 Terminal 33 Low Frequency
20 - 4999 Hz * 20 Hz
5-56 Terminal 33 High Frequency
21 - 5000 Hz * 5000 Hz
5-57 Term. 33 Low Ref./Feedb. Value
-4999 - 4999 * 0.000
5-58 Term. 33 High Ref./Feedb. Value
-4999 - 4999 * 50.000
6-** Analog In/Out
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
1 - 99 s * 10 s
6-01 Live Zero TimeoutFunction
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max speed
[5] Stop and trip
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage
0.00 - 9.99 V * 0.07 V
6-11 Terminal 53 High Voltage
0.01 - 10.00 V * 10.00 V
6-12 Terminal 53 Low Current
0.00 - 19.99 mA * 0.14 mA
6-13 Terminal 53 High Current
0.01 - 20.00 mA * 20.00 mA
6-14 Term. 53 Low Ref./Feedb. Value
-4999 - 4999 * 0.000
6-15 Term. 53 High Ref./Feedb. Value
-4999 - 4999 * 50.000
6-16 Terminal 53 Filter Time Constant
0.01 - 10.00 s * 0.01 s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2* Analog Input 2
6-22 Terminal 60 Low Current
0.00 - 19.99 mA * 0.14 mA
6-23 Terminal 60 High Current
0.01 - 20.00 mA * 20.00 mA
5. Parameter Lists VLT Micro Drive FC 51
78
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 51 Series and is the answer not in the manual?

Danfoss VLT FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 51 Series
CategoryDC Drives
LanguageEnglish

Related product manuals