Parameter Range Default Function
1-73 Flying Start [0] Disabled
[1] Enabled
0
Select [1] Enable to enable the
adjustable frequency drive to catch a
spinning motor
3-41 Ramp 1 Ramp Up Time 0.05–3600.0 s Size related Ramp-up time from 0 to rated
1-23 Motor Frequency
3-42 Ramp 1 Ramp Down Time 0.05–3600.0 s Size related Ramp-down time from rated
1-23 Motor Frequency to 0
4-12 Motor Speed Low Limit
[Hz]
0.0–400 Hz 0.0 Hz Enter the minimum limit for low
speed
4-14 Motor Speed High Limit
[Hz]
0.0–400 Hz 2.56 [65] Enter the maximum limit for high
speed
4-19 Max Output Frequency 0–400 Size related Enter the maximum output frequency
value
Table 6.6 Motor Parameters
How to Program Design Guide
MG18C522 Danfoss A/S © Rev. 2014-01-14 All rights reserved. 83