GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 116 of 123
7580 EIC warning
No. Setting Min. setting Max. setting Factory
setting
7581 EIC warning Delay 0.0 s 100.0 s 0.0 s
7582 EIC warning Relay output A Not used Option-
dependent
Not used
7583 EIC warning Relay output B Not used Not used
7584 EIC warning Enable OFF ON OFF
7585 EIC warning Fail class ML-2 unit dependent Warning
7590 EIC shutdown
No. Setting Min. setting Max. setting Factory
setting
7591 EIC shutdown Delay 0.0 s 100.0 s 0.0 s
7592 EIC shutdown Relay output A Not used Option-
dependent
Not used
7593 EIC shutdown Relay output B Not used Not used
7594 EIC shutdown Enable OFF ON OFF
7595 EIC shutdown Fail class ML-2 unit dependent Shutdown
7600 EIC overspeed
No. Setting Min. setting Max. setting Factory
setting
7601 EIC overspeed Set point 0 % 400 % 110 %
7602 EIC overspeed Delay 0.0 s 100.0 s 2.0 s
7603 EIC overspeed Relay output A Not used Option-
dependent
Not used
7604 EIC overspeed Relay output B Not used Not used
7605 EIC overspeed Enable OFF ON OFF
7606 EIC overspeed Fail class ML-2 unit dependent Warning
7610 EIC coolant t. 1
No. Setting Min. setting Max. setting Factory
setting
7611 EIC coolant t. 1 Set point -40 deg. 210 deg. 100 deg.
7612 EIC coolant t. 1 Delay 0.0 s 100.0 s 5.0 s
7613 EIC coolant t. 1 Relay output A Not used Option-
dependent
Not used
7614 EIC coolant t. 1 Relay output B Not used Not used
7615 EIC coolant t. 1 Enable OFF ON OFF
7616 EIC coolant t. 1 Fail class ML-2 unit dependent Warning
7620 EIC coolant t. 2
No. Setting Min. setting Max. setting Factory
setting
7621 EIC coolant t. 2 Set point -40 deg. 210 deg. 110 deg.
7622 EIC coolant t. 2 Delay 0.0 s 100.0 s 5.0 s
7623 EIC coolant t. 2 Relay output A Not used Option-
dependent
Not used
7624 EIC coolant t. 2 Relay output B Not used Not used
7625 EIC coolant t. 2 Enable OFF ON OFF
7626 EIC coolant t. 2 Fail class ML-2 unit dependent Warning