GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 115 of 123
7510 Modbus comm. settings
No. Setting Min. setting Max. setting Factory
setting
7511 Modbus comm. ID 1 247 1
7512 Modbus comm. Speed 9600 Baud 19200 Baud 9600 Baud
7513 Modbus comm. Mode RTU ASCII RTU
7520 Modbus comm. error
No. Setting Min. setting Max. setting Factory
setting
7521 Modbus comm. error Delay 1.0 s 100.0 s 10.0 s
7522 Modbus comm. error Relay output A Not used Option-
dependent
Not used
7523 Modbus comm. error Relay output B Not used Not used
7524 Modbus comm. error Enable OFF ON OFF
7525 Modbus comm. error Fail class Alarm Trip MB Warning
7560 Engine I/F
7570 EIC comm. error
No. Setting Min. setting Max. setting Factory
setting
7571 EI comm. error Delay 0.0 s 100.0 s 0.0 s
7572 EI comm. error Relay output A Not used Option-
dependent
Not used
7573 EI comm. error Relay output B Not used Not used
7574 EI comm. error Enable OFF ON OFF
7575 EI comm. error Fail class ML-2 unit dependent Warning
No. Setting Min. setting Max. setting Factory
setting
7561 Engine I/F Engine type OFF
DDEC
EMR
JDEC
Iveco
Perkins
Caterpillar
Volvo Penta EMS
Volvo Penta EMS 2
Scania EMS
Scania EMS S6
MDEC 2000/4000 M.302
MDEC 2000/4000 M.303
MTU ADEC
Cummins CM850
Generic J1939
OFF
7562 Engine I/F Node CANopen ID
1 128 6
7563 Engine I/F EIC Controls
ON OFF ON
7564 Engine I/F EIC Auto View
ON OFF ON
Please choose MDEC 2000/4000 M.303, when M.201 or M.304 is required.
Menu 7562 is only used when MTU ADEC is selected as engine type.