GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 121 of 123
10800-10950 Water temp. config. sensor
No. Setting Min. setting Max. setting Factory
setting
10800 VDO Type 1 5 1
10810 VDO 3 Water temp. Input 1 0 ohm 2500 ohm 0 ohm
10820 VDO 3 Water temp. Output 1 0 150 0 °C
10830 VDO 3 Water temp. Input 2 0 ohm 2500 ohm 40 ohm
10840 VDO 3 Water temp. Output 2 0 150 40 °C
10850 VDO 3 Water temp. Input 3 0 ohm 2500 ohm 60 ohm
10860 VDO 3 Water temp. Output 3 0 150 60 °C
10870 VDO 3 Water temp. Input 4 0 ohm 2500 ohm 80 ohm
10880 VDO 3 Water temp. Output 4 0 150 80 °C
10890 VDO 3 Water temp. Input 5 0 ohm 2500 ohm 90 ohm
10900 VDO 3 Water temp. Output 5 0 150 90 °C
10910 VDO 3 Water temp. Input 6 0 ohm 2500 ohm 100 ohm
10920 VDO 3 Water temp. Output 6 0 150 100 °C
10930 VDO 3 Water temp. Input 7 0 ohm 2500 ohm 120 ohm
10940 VDO 3 Water temp. Output 7 0 150 120 °C
10950 VDO 3 Water temp. Input 8 0 ohm 2500 ohm 150 ohm
10960 VDO 3 Water temp. Output 8 0 150 150 °C
10970-11000 Engineering units
No. Setting Min. setting Max. setting Factory
setting
10971 Unit Set point C/bar F/bar C/bar
10980 Configurable input selection
No. Setting Min. setting Max. setting Factory
setting
10980 Conf inp 1 Set point VDO Binary VDO
10990 Conf inp 2 Set point VDO Binary VDO
11000 Conf inp 3 Set point VDO Binary VDO
Possible selections:
- VDO
- 4 to 20 mA
- 0 to 20 mA
- Binary