GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 37 of 123
22. Island mode
Change genset mode to “Island”
23. GB close inhibit
Inhibit used for GB, where ext. PLC or other equipment controls when load is on genset.
Configuration of the digital alarm inputs
The digital inputs are configured via the utility software (USW).
Remember to write the settings to the unit.
Use this button to upload the menu.
The individual I/O number and the function
are now selected. In the example below,
‘Digital input 1’ is chosen and a terminal
number must be assigned to the input. If the
input is used as alarm input, then the name
can be changed to the relevant name
selected from the predefined list below.
3000-3050 Digital input term. 10 to 15, without wire break detection
Then name the input. This can be done in translation.
If nominal setting is going to be selected by a binary input, M-Logic must be
used.