GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 38 of 123
Complete the input settings and select the appropriate fail class and outputs. The outputs A and
B can be used to activate one or two of the configurable relay outputs or LEDs. If the relay
function is set as a limit relay, no warning pop-up will be shown in the display. The relay 0 is a
virtual relay, so both output A and B must be set to limit relays if no warning in the display is
wanted.
Remember to activate the function by marking the
Enable tick box.
If the alarm is only to be active when the genset is
running, the inhibit settings must be used. If for
example “Not run status” is ticked in the inhibit
settings, it means that the alarm is inhibited until the
running feedback is present, when the Run status
timer has not yet expired.
If the High Alarm is set, the alarm will be registered
upon a closing contact. If the High Alarm is not set,
the alarm will be registered upon an opening contact.