 P6-xx  PR Parameters (Please refer to Chapter 7 for detailed setting) 
P6-00    ODEF  Homing Definition 
Address: 0600H 
0601H 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section; 
7.10 
 
Default: 
0x00000000 
 
Control 
Mode: 
PR 
 
Unit: 
- 
 
Range: 
0x00000000 ~ 0x10FFFF3F 
 
Data Size: 
32-bit 
 
Format: 
Hexadecimal 
 
Settings: 
Homing definition: 
.31 ~ 
28 
.27 ~ 
24 
.23 
~20 
.19 ~ 
16 
.15 ~ 
12 
11 ~ 8  7 ~ 4  3 ~ 0 
BOOT -  DLY  - DEC1 ACC  PATH 
 
PATH: Path type (64-bit) 
0: Stop: Homing complete and stop 
1 ~ 3F: Auto: Homing complete and execute the specified path 
(Path#1 ~ Path#63) 
ACC: Select 0~F for acceleration time and corresponds to          
P5-20~P5-35. 
DEC1: The deceleration time selection of 1
st
 homing, the          setting 
value of DEC is 0~F and corresponds to P5-20 ~ P5-35. 
DLY: Select 0~F for the delay time and corresponds to P5-40 ~ P5-55 
BOOT: When the servo drive applies to the power, if it will be executed 
searching the origin. 
0: Do not do homing 
1: Execute homing automatically (SRV ON for the first time 
after applying to power) 
Apart from the above mentioned definition, the related setting of 
homing also includes: 
1.  P5-04 Homing mode 
2.  P5-05 ~ P5-06 Speed setting of searching the origin 
3.  P6-01: ORG_DEF is the location of the origin. It may not be 0. This 
function is the offset of coordinate system. 
 
A.  After the origin is found (Sensor or Z); it has to decelerate to stop. 
The stop position will exceed the origin for a short distance.