71ECB-VAVS Preloaded Applications
Input Configuration
Parameter Binary
Code
Default Valid
Choices
Description
UI1TYPE
0
1
2
3
x
1
2
3
4
NONE
SPAC
OCC
CONT
Not Configured
Room Temperature Sensor
Occupancy Detection
Window Contact
UI2TYPE
0
4
8
12
16 x
1
2
3
4
5
NONE
DISC
OCC
CONT
SETP
Not Configured
Discharge Air Temperature Sensor
Occupancy Detection
Window Contact
Room Temperature Setpoint Offset
UI3TYPE
0
32
64
x 1
2
3
NONE
4-20
0-5
Not Configured
4-20mA CO
2
Sensor (0-2000 ppm)
0-5V CO
2
Sensor (0-2000 ppm)
COMSENS SP
0
128
x 1
2
DUAL
OFFS
Cooling and Heating Setpoint via EC-Smart-Vue
Room Temperature Setpoint Offset
SENSORS TYPE
0
256
x 1
2
10-2
10-3
Sensors are 10K Type II
Sensors are 10K Type III
Default Input Code 17
Output Configuration
Parameter Binary
Code
Default Valid
Choices
Description
HEAT1
0
1
2
3
4
5
6
7
x
1
2
3
4
5
6
7
8
NONE
DIG
PWM TRIAC
PWM VLV
THERM VLV
0-10V
2-10V
FLOAT VLV
No Reheat
Digital Reheat on DO1
Modulating PWM on DO1 and AO4
PWM Valve on DO1
Thermal Valve on DO1
Modulating 0-10V on AO4
Modulating 2-10V on AO4
Floating Valve (120 sec drive time) on DO1 & DO2
HEAT2
0
8
16
24
32
40
48
x
1
2
3
4
5
6
7
NONE
DIG
PWM TRIAC
PWM VLV
THERM VLV
0-10V
2-10V
No Reheat
Digital Reheat on DO2
Modulating PWM on DO2
PWM Valve on DO2
Thermal Valve on DO2
Modulating 0-10V on AO4
Modulating 2-10V on AO4
HT1 NORM OPEN
0
64
x 1
2
NO
YES
Heating1 Normally Close Valve
Heating1 Normally Open Valve
HT2 NORM OPEN
0
128
x 1
2
NO
YES
Heating2 Normally Close Valve
Heating2 Normally Open Valve
Default Output
Code
9
* DO3 is unused
Configuration Codes

Table of Contents