EasyManua.ls Logo

dIXEL IPC400D SERIES - Pump-Down Active in Shut-Down and in Re-start, Based on the Analogue Input Relative to the Evaporation Pressure.; Timed Pump Down Function; Pump Down Alarm in Start-Up and Stopping

dIXEL IPC400D SERIES
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
!
USER MANUALRelease 1.2 of 01/01/2010 Page 118 of 191
Version: 02/03/2010
2.1. The deactivation pressure of the pump-down pressure switch is higher than the deactivation
pressure of the LP pressure switch: in this case, the rising pressure will deactivate the LP
pressure switch before the pump-down pressure switch, therefore there is no risk of LP alarms
on re-start. If the deactivation of the pup-down pressure switch takes place within time PD04,
from the opening of the solenoid valve, the compressor/step is activated. If this is not the case,
there will be a pump down alarm on start-up.
2.2. The deactivation pressure of the pump-down pressure switch is lower than the deactivation
pressure of the LP pressure switch: in this case the rising pressure will deactivate the pump-
down pressure switch before the LP pressure switch. From the time of deactivation of the
pump-down pressure switch, if the rising pressure deactivates the LP pressure switch within
time AL01, the compressor/step will be activated. If this is not the case, a LP alarm will be
signalled, managed with standard methods.
3. AL02=2: the compressor/step remains active and the pressure continues to decrease until dropping
below the activation threshold of the pump-down pressure switch (supposing that this occurs within
time PD04). The compressor/step is switched-off only at this point. On the successive activation
request of a compressor in the circuit in question, the circuit solenoid valve is activated to favour the
re-equilibrium of the pressure inside the circuit. The compressor/step is not enabled on working while
the pump-down pressure switch remains active. If the deactivation of the pup-down pressure switch
takes place within time PD04, from the opening of the solenoid valve, the compressor/step is
activated. If this is not the case, there will be a pump down alarm on start-up.
44.6.4 Pump-down active in shut-down and in re-start, based on the analogue input relative to the
evaporation pressure.
The behaviour is the same as described in the 2 previous examples depending on the thresholds set at
parameters PD02 and PD03.
44.7 TIMED PUMP DOWN FUNCTION
Timed pump down can be managed by setting parameters PD05 and PD06.
WARNING:
The enabling of the timed pump down function disables all other types of working inherent to this function.
Par. PD05 Pump down time in start-up
0 = function disabled
! 0 function enabled for the set time
Par. PD06 Pump down time in stop
0 = function disabled
! 0 function enabled for the set time
44.8 PUMP DOWN ALARM IN START-UP AND STOPPING
It is possible to manage the reset and memorisation in the historical alarms of the pump down alarms in
start-up and stopping by means of the Pd family parameters.
Par. Pd07 Maximum number of pump down alarm interventions/hour in stopping
exceeding which the alarm is recorded and signalled with code on the display and the alarm relay+ buzzer
are activated
Reset is always manual if Pd07 = 0
Reset is always automatic if Pd07 = 16
Reset passes from automatic to manual if Pd07 goes from 1 to 15
Par. Pd08 Maximum number of pump down alarm interventions/hour in start-up
exceeding which the alarm becomes with manual reset, it is recorded and the alarm + buzzer are activated
Reset is always manual if Pd08 = 0
Reset is always automatic if Pd08 = 16
The reset passes from automatic to manual if Pd08 goes from 1 to 15 and on the basis of the configuration
of Par. Pd09
Par. Pd09 Enabling of pump down alarm in start-up automatic or manual reset if the number of hourly
interventions is reached Pd08

Table of Contents