USER MANUALRelease 1.2 of 01/01/2010 Page 21 of 191
Version: 02/03/2010
60. Auxiliary output n° 1 pressure probe (4÷20 mA / 0÷ 5 Volt)
61. Auxiliary output n° 2 pressure probe (4÷20 mA / 0÷ 5 Volt)
62. Auxiliary output n° 3 pressure probe (4÷20 mA / 0÷ 5 Volt)
63. Auxiliary output n° 4 pressure probe (4÷20 mA / 0÷ 5 Volt)
64. Dynamic set-point 4÷20 mA probe
65. NTC probe on remote terminal n. 1 (function not available)
66. NTC probe on remote terminal n. 2 (function not available)
Digital input (o1-c113, see relevant configurations)
4.4 CONFIGURATION OF THE OUT1 / OUT4 PROPORTIONAL OUTPUTS
0÷10V output signal
0. Output disabled
1. 0÷10V proportional output for circuit n° 1 fan speed control
2. 0÷10V proportional output for circuit n° 2 fan speed control
3. 0÷10V proportional output for circuit n° 3 fan speed control
4. 0÷10V proportional output for circuit n° 4 fan speed control
5. 0÷10V dampers control proportional output / free-cooling mixer valve
6. 0÷10V hot water three-way valve control 0÷10V proportional output
7. 0÷10V auxiliary output n° 1
8. 0÷10V auxiliary output n° 2
9. 0÷10V auxiliary output n° 3
10. 0÷10V auxiliary output n° 4
11. Circuit n° 1 compressor 1 0÷10V modulating output
12. Circuit n° 2 compressor 1 0÷10V modulating output
13. Circuit n° 3 compressor 1 0÷10V modulating output
14. Circuit n° 4 compressor 1 0÷10V modulating output
External relay driving ON/OFF output (o1-c187, see relevant configurations)
4.5 CONFIGURATION OF THE OUT5 / OUT6 PROPORTIONAL OUTPUTS
4÷20mA - 0÷10V - PWM configurable output signal
From 0 to 14 as Out1-Out4 configuration
15. Circuit N° 1 external phase-cut command PWM signal = TF 1
16. Circuit N° 2 external phase-cut command PWM signal = TF 2
17. 4÷20mA proportional output for circuit n° 1 fan speed control
18. 4÷20mA proportional output for circuit n° 2 fan speed control
19. 4÷20mA proportional output for circuit n° 3 fan speed control
20. 4÷20mA proportional output for circuit n° 4 fan speed control
21. 4÷20mA dampers control proportional output / free-cooling mixer valve
22. 4÷20mA hot water three-way valve control proportional output
23. 4÷20mA auxiliary output n° 1
24. 4÷20mA auxiliary output n° 2
25. 4÷20mA auxiliary output n° 3
26. 4÷20mA auxiliary output n° 4
27. Circuit n° 1 compressor 1 4÷20mA modulating output
28. Circuit n° 2 compressor 1 4÷20mA modulating output
29. Circuit n° 3 compressor 1 4÷20mA modulating output
30. Circuit n° 4 compressor 1 4÷20mA modulating output
External relay driving ON/OFF output (o1-c187, see relevant configurations)

Table of Contents