57.17 CIRCUIT BREAKER ALARM
Display label meaning
C1tr (compressor n° 1 circuit breaker alarm) -…C16tr (compressor n° 16
circuit breaker alarm)
Cause of activation
The alarm is not detected for AL27 on compressor switch-on
With ID active
The alarm is not detected with compressor off if AL30=0
Reset
If ID not active
Reset
Manual. If more than AL28 compressor interventions occur per hour. Enter the
functions menu to reset the alarm (see procedure in cOtr function functions
menu)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
it follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
It follows its regulation
Support/boiler/anti-freeze
It follows/they follow its/their regulation
Pump/and water evaporator
and condenser
It follows its regulation
Compressor affected
Always off
Compressors not affected
If Par. AL29 = 0 following their regulation
If Par. AL29 = 1 off
Pump down solenoid valve
It switches-off if there is only 1 compressor per circuit, otherwise it follows its
regulation
AL27 Compressor 1 - 6 circuit breaker alarm delay on start-up
Allows to set a delay time when recognising the circuit breaker alarm on compressor start-up.
AL28 Maximum number of compressor 1 - 6 circuit breaker interventions per hour
It determines a maximum number of compressor circuit breaker alarm interventions per hour. When these
are exceeded the alarm passes from automatic to manual reset.
AL29 compressor circuit breaker alarm working
1= the compressor circuit breaker alarm only blocks the compressor of interest
2= the compressor circuit breaker alarm blocks the compressor of interest and all compressors present in
that circuit
SEE RESET PROCEDURE IN COMPRESSOR 1 - 6 CIRCUIT BREAKER FUNCTIONS MENU AFTER
AL28 INTERVENTIONS PER HOUR